Model YEM311AG single phase electronic front board installed active energy meter is a kind of new style single phase two wire active energy meter, it adopts micro-electronics technique, and imported large scale integrate circuit, uses advanced technique of digital and SMT techniques, etc. The meter completely accords with relevant technical requirements of class 1 single phase active energy meter stipulated in international standard IEC 62053-21. It can accurately and directly measure 50Hz or 60Hz active energy consumption from single phase AC electricity net, it is used for setting indoor or outdoor, and it can display total energy consumption by step motor type impulse register. It has following features: good reliability, small volume, light weight, specious nice appearance, convenient installation, etc.
Specification
Model |
Accuracy |
Reference Voltage |
Current Specification |
Starting Current |
Insulation Performance |
YEM311AG |
Class 1 |
127/230V |
5(30)A 10(60)A 20(100)A |
0.02A 0.04A 0.08A |
AC voltage 4kv for 1 min, 1.2/50us waveform impulse voltage 6kv |
* If you need different reference voltage or current specification, please advisory our sales personnel.
Competitive Advantage
1. Tests and manufacturing the meter meets this Specification and the following IEC Standards : IEC 62053 -21 Electricity Metering Equipment (AC) Particular Requirements Part 21 Static Meters for Active Energy (Ciass1).
2. The meter is factory calibrated and no adjustment of calibration is needed outside the factory facilities.
3. The insulating materials used in the construction of meters is non- hygroscopic, non-aging and of tested quality.
4. The meter is of compact modern design with no moving parts, convenient to transport and immune to shocks and vibrations during transportation and handling.
5. The meter is designed with application specific integrated circuit and manufactured using Surface Mount Technology (SMT).
6. The meter cover has one transparent window at the front for reading of all the displayed values and parameters, name plate details and observation of all the operation indicators.
7. The meter-base, meter cover, terminal block &terminal block cover is made of unbreakable high grade, fire resistant, non-flammable reinforced polycarbonate to ensure reasonable safety against spread of fire.
8. Standard configuration 5+1 digits display (99999.1kWh) by step motor type impulse register. May select 6+1 digits display (Product Configuration code is AK).
9. All parts of the meters likely to develop corrosion during operating life shall be effectively protected with suitable protective coating.
10. Standard configuration only one LED instructions signal of energy impulse (red), may select add instructions power supply state (green)and automatic detection the direction of the flow of load current and instructions by LED (when display yellow, that is meaning the direction of the flow of load current reverse). Please specified when ordering.
11. Direct connect operation, there are two types wiring you may select. Standard configuration type 1B wiring, may select type 1A wiring (Product Configuration code is TG).
12. The terminal is suitable for copper or aluminum conductors of sizes up to 16 MM. The manner of fixing the conductors to the terminal shall ensure durable contact so that there is no risk of losing or undue heating of the conductors or the terminals.
Dimension